Parametric equations for design of fire insulation coating thickness of steel columns

Document Type : Original Research

Authors
1 Ph. D. Student
2 Professor
Abstract
This paper investigates the effects of various parameters, including support conditions, the Demand to Capacity Ratio (DCR) of the member under gravitational loads, the section factor (the ratio of perimeter to area), and the fire insulation coating thickness on the fire resistance duration of steel columns under fire effects. To this end, four steel H-shaped columns and four steel tube columns with the height of 4 meters, are subjected to the standard fire curve (ASTM E119) from four sides, and the effects of different parameters are studied. Initially, a heat transfer analysis is carried out on the 2D cross-section of columns with its fire insulation coating in Abaqus software. Then, a nonlinear general static analysis is performed on a 3D steel column model subjected to gravity (concentrated axial) and thermal loading simultaneously.

Results of this study indicate that the columns only expand but do not deform significantly until approximately 250oC. After that, a decrease in the steel strength and stiffness and as a result, a decrease in fire resistance and bearing capacity of the steel column occurs. This is accompanied by an increase in the mid-span horizontal displacement of the column and an increase in the effect of the P-δ bending moment, which results in the column failure at about 500oC to 650oC. The results also show that the fixed or pin support condition on the bottom end of the column does not significantly affect the column failure time under fire effects. In square box columns, the increase in the section thickness increases the fire resistance duration of the steel column. However, increasing the section width does not significantly affect the column failure time. In H-shaped columns, the increase in the flange thickness and the decrease in the column web height increases the column fire resistance duration. On the other hand, the results indicate that the section factor, the initial load level of the member due to gravitational loads, and the fire insulation coating thickness have a significant effect on column failure time to the extent that with the increase in DCR of the member from 0.3 to 0.7, the failure time of the column decreases by about 25 to 35 minutes.

Based on the results of this study, two formulae have been presented to calculate the failure time of protected columns by CAFCO300. The results of these formulae have also been compared to a relationship proposed in Chapter 10 of the Iranian National Building Regulations. It is found that the results of these formulae are fairly similar, when the initial DCR equals 0.7. Therefore, the relationships of the present study provide a more optimal and accurate design of the fire insulation coating thickness, because this load level can only occur in structures that are not designed for lateral loads and are designed only under gravitational loads.

Keywords

Subjects


1. Bažant Z., Zhou Y. 2002, Why did the world trade center collapse? Simple analysis, 128(1), 2-6.
2. Kotsovinos P., Usmani A. 2013, The World Trade Center 9/11 disaster and progressive collapse of tall buildings, 49, 741-65.
3. Behnam B. 2019, Fire structural response of the plasco building: A preliminary investigation report, 17(5), 563-80.
4. Shakib H., Pirizadeh M., Dardaei S., Zakersalehi M. 2018, Technical and administrative assessment of Plasco building incident, 16,1227-39.
5. Chaboki M., Heshmati M., Aghakouchak A.A. 2021, Investigating the Behaviour of steel framed-tube and moment-resisting frame systems exposed to fire, Structures Journal.
6. Qin C., Mahmoud H. 2019, Collapse performance of composite steel frames under fire, 183, 662-76.
7. Jiang J., Li G., 2017, Disproportionate collapse of 3D steel-framed structures exposed to various compartment fires, 138, 594-607.
8. Jiang J., Zhang C. 2018, Simulating the Response of a 10-Storey Steel-Framed Building under Spreading Multi-Compartment Fires, 7(4), 389-96.
9. Venkatachari S., Kodur V. 2020, System level response of braced frame structures under fire exposure scenarios, 170, 106073.
10. Kraus P., Mensinger M., Tabeling F., Schaumann P. 2015, Investigations of steel elements with intumescent coating connected to space-enclosing elements in fire.
11. Podolski D. 2017, Temperature distribution in intumescent coating protected steel sections: The University of Manchester (United Kingdom).
12.Hautala J., Kangashaka I., Malaska M., Pajunen S. 2021, Resistance of partially protected steel beams in fire, 4(2-4), 1849-55.
13. Anvari A, Torra-Bilal I., Mahamid M.,2019, The Behavior of Structural Steel Elements with Damaged Fire Protection Material. Structures Congress 2019; American Society of Civil Engineers Reston, VA.
14. Zakwan F., Krishnamoorthy R., Ibrahim A., Ismail R., 2020, Finite Element Analysis of Coated (Intumescent Coating Protection) Cellular Steel Beam (CSB) Expose to Fire. IOP Conference Series: Materials Science and Engineering; IOP Publishing.
15. Li G., Wang P., Wang Y. 2010, Behaviour and design of restrained steel column in fire, Part 1: Fire test, 66(8-9), 1138-47.
16. Wang P., Wang Y., Li G. 2010, Behaviour and design of restrained steel column in fire: Part 2. Parameter study, 66(8-9), 1148-54.
17. Agarwal A., Choe L., Varma A. 2014, Fire design of steel columns: Effects of thermal gradients, 93, 107-18.
18. Dwaikat M., Kodur V., Quiel S., Garlock M. 2011, Experimental behavior of steel beam–columns subjected to fire-induced thermal gradients, 67(1), 30-8.
19. Li G., Wang W., Chen S. 2009, A simple approach for modeling fire-resistance of steel columns with locally damaged fire protection, 31(3), 617-22.
20. Jin H., Chun Q. 2020, Research on fire-resistance capacities of steel columns with partial-damaged fire protection coating, 24(6), 1893-902.
21. Inc A. ABAQUS Analysis User’s Manual, Version 6.14. 2014.
22. B. Standard. 2005, Eurocode 3-Design of Steel Structures: Part 1–2: General Rules–Structural Fire Design. European Committee for Standardization Brussels, Belgium.
23. B. Standard. 2002, Eurocode 1-Actions on structures: part 1-2: General actions: actions on structures exposed to fire Design. European Committee for Standardization Brussels, Belgium.
24. MHUD. 2023, "Iranian National Building Code 10, steel structure design. Tehran (Iran)." In.: Ministry of Housing and Urban Development (In Persian).
25. Beyler C., Beitel J., Iwankiw N., Lattimer B. 2007, Fire resistance testing for performance-based fire design of buildings, Final report, The Fire Protection Research Foundation Quincy, Quincy.
26. BS 476-20. 1987, "Fire Tests on Building Materials and Structures – Part 20:Method for Determinationof the Fire Resistance of Elements of Construction (General Principles)." BSI, UK.